Description
The Crowcon Xgard Bright is a fixed detector for flammable and toxic gas detection and oxygen monitoring. The Crowcon Xgard Bright is designed to provide ease of operation and reduced installation costs. The Xgard Bright provides analogue 4-20mA and RS-485 Modbus signals as standard, comes with an Alarm and Fault relay as standard as well as optional HART communications.
Using the Crowcon Xgard Bright lowers the cost of installation, and the 4-wire addressable implementation drastically reduces the cabling requirements. The large OLED display allows users to easily work with Xgard Bright during install, calibration and routine maintenance without the need to open the housing.
The Crowncon Xgard Bright is available with MPS (Molecular Property Spectomete) technology, and is suited for a wide range of gases and sensor types.
Range of flammable gases | MPS | 0-100% LEL |
Hydrogen sulphide (H2S) | Electrochemical | 10, 20, 25, 50, 100, 200 ppm |
Oxygen (O2) | Oxygen | 0-25% vol |
Carbon Monoxide (CO) | Electrochemica | 0-25, 50, 100, 200, 250, 300, 1000, 2000 ppm |
Methane (CH4) | Pellistor | 0-100% LEL |
Pentane (C5H12) | Pellistor | 0-100% LEL |
Hydrogen (H2) | Pellistor | 0-100% LEL |
LPG | Pellistor | 0-100% LEL |
Carbon Dioxide (CO2) | Infra-Red | 0-5% vol |
VOC* | PID | 0-1000 PPM |
Methane (CH4) | Infra-Red | 0-100% LEL |
Propane (C3H8) | Infra-Red | 0-100% LEL |
Ammonia (NH3)* | Electrochemical | 0-50, 100 ppm |
Chlorine (CL2)* | Electrochemical | 0-5, 10 ppm |
Ozone (O3)* | Electrochemical | 0-1 ppm |
Sulpur dioxide (SO2)* | Electrochemical | 0-10 ppm |
Butane (C4H10) | Infra-Red | 0-100% LEL |
Pentane (C5H12) | Infra-Red | 0-100% LEL |
LPG | Infra-Red | 0-100% LEL |
Hydrogen Cyanide (HCN)* | Electrochemical | 0-25 ppm |
Hydrogen Peroxide (H2O2)* | Electrochemical | 0-5 ppm |
* Safe Area Only
Additional information
Enclosure | ADC 12 aluminum alloy |
---|---|
Dimensions | 156 x 166 x 109mm (6.1 x 6.5 x 4.3inch) |
Weight | Aluminum alloy 1kg (2.2lbs) |
IP Rating | IP65, IP66 (with weatherproof cap) |
Cable Entry | 2x M20 (stopping plug fitted to left-side entry) or supplied with ½” NPT adapters |
Power | 10-30Vdc. 3W max |
Electrical Output | 4-20mA current sink or source, HART (optional), RS-485 Modbus RTU |
Relays | Alarm 1, Alarm 2, Fault SPST contacts rated 1A 30Vdc |
Sounder out | 24Vdc (nominally), 250mA maximum load |
Temperature Range | -40°C to +70°C |
Relative Humidity | 0 to 95% RH, non-condensing |
Repeatability | +/- 2% FSD |
Zero drift | +/- 2% FSD per year maximum |
Approvals | ATEX/IECEx, Ex II 2D Ex tb IIIC T80°C Db, Ex II 2G Ex db IIC T6 Gb |
Standards | EN60079-0:2012 + A11:2013, EN60079-1:2014, EN60079-31:2014, IEC60079-0:2017 Edition 7, IEC60079-1:2014-06, IEC60079-31:2013 |
Zones | Certified for use in Zone 1 and Zone 2 areas |
EMC compliance | EN50270:2015 |
Subtype | Electrochemical, Infrared, Oxygen, Pellistor |
Material | Aluminium |
Gas Type | Carbon Monoxide 0-1000ppm, Carbon Monoxide 0-100ppm, Carbon Monoxide 0-2000ppm, Carbon Monoxide 0-250ppm, Carbon Monoxide 0-500ppm, Carbon Monoxide 0-50ppm, Hydrogen 0-100%LEL, Hydrogen sulphide (H2S) 0-100ppm, Hydrogen sulphide (H2S) 0-25ppm, Hydrogen sulphide (H2S) 0-50ppm, Hydrogen Sulphide 0-200ppm, Infrared Carbon Dioxide 0-5% VOL, Infrared LPG 0-100% LEL, Infrared Methane 0-100% LEL, Infrared Propane 0-100% LEL, LPG 0-100% LEL, Methane 0-100% LEL, Oxygen 0-25% VOL |
HART | HART disabled, HART enabled |