Description
The Ampac 4310-0095 is an Universal High Level Interface Board which provides the ability for the FireFinder Marine Fire Panel to interface the range of high-level interface options using common communication protocols.
The individual Fire Alarm Control Panel events such as fire, pre-alarms, disablements/isolates and faults can be configured to be passed to the various external systems for reporting and indication.
Features
Easy to configure
Supports RS232 and RS485 communications interfaces to external systems.
Voyage Data Recorder (VDR) interfacing converts system status, alarms, and events to NMEA 0183 Standard compliant strings.
Additional information
Voltage | 27.5 V dc +/- 0.1 V dc |
---|---|
Quiescent Current | 37.5 mA |
Data Output | RS485 and RS232 ASCII Characters |
BAUD Rate | 4800 and 38400 |
Data Bits | 8 (D7=0) |
Parity | |
Stop Bits | 1 |
Temperature Range | -5°C to +70°C |
Relative Humidity | 0 to 95% RH, non-condensing |
Dimensions | 500mm H x 405mm W x 150mm D |